XLPE Insulated, PVC Sheathed Unarmored Multicore control Cables 0.6/1kV
Application
These cables are used for control circuits unenclosed, enclosed in conduit, buried direct or in underground ducts for commercial, industrial, mining and electricity authority systems where not subject to mechanical damage.
Standard
- AS/NZS 5000.1
- AS/NZS 3008
- AS/NZS 1125
Cable Construction
CONDUCTOR | Plain annealed copper. |
INSULATION | XLPE X-90. |
INSULATION COLOUR: | 3C – Red, White, Blue 4C - Red, White, Blue,black |
SHEATH: | Polyvinylchloride compound PVC 5V-90 |
SHEATH COLOUR: | Black, other colors are available upon request |
Technical Characteristics
CONDUCTOR | CURRENT RATINGS | ELECTRICAL CHARACTERISTICS | |||||
NOMINAL AREA MM2 | UNENCLOSED IN AIR A |
BURIED DIRECT A | BURIED IN DUCTS A | MAXIMUM DC RESISTANCE @20°C OHM/KM |
MAXIMUM AC RESISTANCE @90°C OHM/KM |
REACTANCE OHM/KM | THREE PHASE VOLTAGE DROP @90°C MV/AM |
10 | 68 | 91 | 68 | 1.83 | 2.33 | 0.084 | 4.05 |
16 | 91 | 118 | 89 | 1.15 | 1.47 | 0.081 | 2.55 |
25 | 121 | 155 | 118 | 0.727 | 0.927 | 0.081 | 1.61 |
Cable Parameter
NOM. CONDUCTOR AREA |
MAIN CONDUCTOR TYPE |
NOM. INSULATION THICKNESS |
NOM. SHEATH THICKNESS |
NOM. OVERALL DIAMETER | APPROX. MASS |
MM2 | MM | MM | MM | KG/KM | |
3 cores | |||||
10 | 7/1.35 | 0.7 | 1.4 | 15.3 | 435 |
16 | 7/1.70 | 0.7 | 1.4 | 17.6 | 625 |
25 | 7/2.14 | 0.9 | 1.4 | 21.5 | 950 |
4 cores | |||||
10 | 7/1.35 | 0.7 | 1.4 | 16.7 | 550 |
16 | 7/1.70 | 0.7 | 1.4 | 19.2 | 800 |
25 | 7/2.14 | 0.9 | 1.4 | 23.6 | 1250 |